When the transformer operates in the power system, it is difficult to avoid some short-circuit events. Depending on the severity of the short-circuit event and the strength of the transformer's anti short-circuit ability, sometimes it is safe and sometimes it is damaged. The damage of a distribution transformer will affect a factory in a short time, while the short-circuit accident of a distribution transformer will affect an urban area, and the replacement is more difficult, and the repair takes 2 3 months. Therefore, improving the short-circuit resistance of power transformer has always been a matter of great concern to the power department, and it is also the main goal of the manufacturing department.
Before the 1990s, there were only four high current laboratories (stations) in Xi'an, Shenyang, Shanghai and Beijing in China. Their facilities are mainly for switching capacity test in the switching industry, but they can also test distribution transformers. Therefore, in the early and mid-1980s, Shenyang
Научно-исследовательский институт трансформаторов отвечал за унифицированную конструкцию распределительных трансформаторов sl7 и старых s9-30 1600 кВА / 10 кВ. Опытные образцы, изготовленные каждым заводом, прошли испытания на короткое замыкание в указанных выше лабораториях (станциях). Испытания прошли 14 sl7 и 12 старых S9. После успешных испытаний был произведен пробный выпуск нового типа S9. Первая партия из 37 единиц прошла испытания, и квалификация нового типа S9 достигла более 90 процентов (Кема в Нидерландах испытывала зарубежные распределительные трансформаторы с разовой квалификацией 50 процентов). К 1996 году в различных лабораториях (станциях) было испытано около 300 распределительных трансформаторов, в том числе типа С7.
For more than ten years, China has done a lot of short-circuit tests on distribution transformers, and improved each damage condition, so that the qualified rate reaches more than 90 percent , much higher than the foreign qualified rate of 50 percent , which has been confirmed in the actual operation of power grid and achieved gratifying results. It can be said that the basic solution to the short-circuit strength of distribution transformer depends on "practical test", which is a very important experience.
В Китае нет базы для испытаний силовых трансформаторов, поэтому определить сопротивление короткого замыкания силовых трансформаторов сложно. В 1986 году Государственная плановая комиссия одобрила строительство сильноточной испытательной станции Shenyang Hushitai, которая была предоставлена в аренду государством и одобрена для консультаций французской компанией EDF. После многих лет работы первая фаза проекта была завершена в конце 1993 года, построена сеть 220кВ и установлены две 1200мВА/0 224кВ. После приемки государственной экспертной комиссией он был введен в эксплуатацию в январе 1994 г., а в 1994 и 1995 гг. было проведено большое количество испытаний распределительных трансформаторов. осуществлена в 1996 году.
Испытание на короткое замыкание силового трансформатора 110 кВ
110kV power transformer is the main transformer in China's transmission and distribution system, and its output accounts for about 1 / 5 of the total output of transformer. According to the statistical data from 1995 to 1996, the short-circuit accident of 110kV transformer accounts for 5O percent of the total accident of this level, and shows an upward trend. Therefore, how to improve the short-circuit resistance of this level of power transformer has become the main topic at the Zengcheng conference in Guangdong. It is recognized that the best way is to verify it with short-circuit test.
From 1996 to the first half of 2005, due to the attention of power departments and manufacturing enterprises, More than 60 factories have successively conducted short-circuit tests on 80 110kV power transformers (including 4 from Shenyang Transformer Co., Ltd., 3 from Xinjiang TBEA Co., Ltd., 2 from Nantong AIA Transformer Co., Ltd., 2 from Changzhou transformer factory, 3 from Yunnan Transformer Factory, 2 from Baoding, 3 from Huapeng, etc.) with a pass rate of >96 процентов. Распределительные трансформаторы с квалификационным коэффициентом выше 10 кВ.
Для того, чтобы пройти первое испытание, эти заводы вложили много человеческих и материальных ресурсов. В процессе разработки продукта они приложили определенные усилия в области дизайна, процесса, производства и управления, что, несомненно, является значительным улучшением комплексного качества предприятий. 28 из 45 изделий, испытанных в первом полугодии 2001 г., работали в сети, а одно с наименьшим временем наработки работало несколько месяцев. Среди них новый продукт подстанции Шэньян, трансформатор 50000 кВА / 110 кВ, который работает уже более пяти лет и приветствуется пользователями. На основе получения данных испытаний эти фабрики улучшили структуру дизайна продукта. Приняв это за стандарт, они были запущены в массовое производство и включены в энергосистему, поэтому в будущем не будет -короткого замыкания.
Статистические данные Уханьского научно-исследовательского института высокого напряжения Государственной энергетической корпорации и Китайского научно-исследовательского института электроэнергетики за период с 1995 по 1999 г. показывают, что количество аварий, связанных с коротким замыканием трансформатора, снизилось с 50 процентов в прошлом до 40 процентов, т.е. в основном за счет повышения надежности работы системы за счет эксплуатации вышеуказанной партии высоконадежных трансформаторов. Следует сказать, что авария короткого-замыкания трансформатора 110В изначально была пресечена.
Испытания на короткое-замыкание трансформатора 110 кВ должны быть дополнительно расширены.
В настоящее время в Китае 60 заводов, которые обычно поставляют силовые трансформаторы на 110 В, и только более 100 заводов провели испытания на короткое-замыкание трансформаторов на 110 кВ, что составляет около 55 процентов. Несколько заводов подготавливают условия для испытаний-на короткое замыкание, для чего требуется сильная поддержка со стороны пользователей и активное внедрение протестированных продуктов, чтобы они играли роль в системе. Что касается заводов-изготовителей, то мы должны провести работы по проектированию и технологии, произвести достаточную материальную подготовку, собрать средства и реализовать их на практике. Следует также отметить, что заводы, которые не проводили испытания трансформаторов на короткое-замыкание, должны использовать время, чтобы не повлиять на заказ и даже не потерять квалификацию производства.